MDR-60-24

DIN rail power supply with universal input – 24V / 2.5A output

  • Universal AC input/Full range
  • Protections: Short circuit / Overload / Over voltage
  • Cooling by free air convection
  • Can be installed on DIN rail TS-35/7.5 OR 15
  • Class I, Div 2 Hazardous Locations T4
  • LED indicator for power on
  • DC OK relay contact
  • No load power consumption < 0.75W
  • 100% full load burn-in test
  • 3 years warranty
Request information
Order online
CODE: 099-8303 Category: Power supplies

Description

Power supply with nominal power of 60W, can provide a maximum current of 2,5A on load at 24Vdc.
The universal input range with 85÷264Vac and 120÷370Vdc allows the use of the power supply in different conditions of the electrical line.
Protected against overload, short circuit and output overvoltage. Equipped with OK output signal and with a trimmer for the voltage adjustment. Small size and DIN rail mounting, ideal power supply for the entire series of compact PLCs and I/O modules.

Technical Specification

OUTPUT
DC VOLTAGE 24V
RATED CURRENT 2.5A
CURRENT RANGE 0 ~ 2.5A
RATED POWER 60W
RIPPLE & NOISE (max.) 150mVp-p
VOLTAGE ADJ. RANGE 24 ~ 30V
VOLTAGE TOLERANCE ±1.0%
LINE REGULATION ±1.0%
LOAD REGULATION ±1.0%
SETUP, RISE TIME 500ms, 30ms/230VAC 500ms, 30ms/115VAC at full load
HOLD UP TIME (Typ.) 50ms/230VAC 20ms/115VAC at full load
INPUT
VOLTAGE RANGE 85 ~ 264VAC 120 ~ 370VDC
FREQUENCY RANGE 47 ~ 63Hz
EFFICIENCY (Typ.) 88%
AC CURRENT (Typ.) 1.8A/115VAC 1A/230VAC
INRUSH CURRENT (Typ.) COLD START 30A/115VAC 60A/230VAC
LEAKAGE CURRENT <1mA / 240VAC
OVERLOAD 105 ~ 150% rated output power
Protection type : Constant current limiting, recovers automatically after fault condition is removed
OVER VOLTAGE 31.2 ~ 36V
Protection type : Shut down o/p voltage, re-power on to recover
DC OK SIGNAL Relay contact rating(max.): 30V/1A resistive
WORKING TEMP. -20 ~ +70℃ (Refer to “Derating Curve”)
WORKING HUMIDITY 20 ~ 90% RH non-condensing
STORAGE TEMP., HUMIDITY -40 ~ +85℃, 10 ~ 95% RH
TEMP. COEFFICIENT ±0.03%/℃ (0 ~ 50℃)
VIBRATION Component:10 ~ 500Hz, 2G 10min./1cycle, 60min. each along X, Y, Z axes
Mounting: Compliance to IEC60068-2-6
SAFETY STANDARDS UL508, UL60950-1, TUV EN60950-1,Class I, Div. 2 Group A, B, C, D Hazardous Locations T4 approved
WITHSTAND VOLTAGE I/P-O/P:3KVAC I/P-FG:2KVAC O/P-FG:0.5KVAC
ISOLATION RESISTANCE I/P-O/P, I/P-FG, O/P-FG:100M Ohms / 500VDC / 25℃/ 70% RH
EMC EMISSION Compliance to EN55011, EN55022 (CISPR22), EN61204-3 Class B, EN61000-3-2,-3
EMC IMMUNITY Compliance to EN61000-4-2, 3, 4, 5, 6, 8, 11, EN55024,EN61000-6-1,EN61204-3,
light industry level, criteria A
MTBF 299.2K hrs min. MIL-HDBK-217F (25℃)
DIMENSION 40*90*100mm (W*H*D)
PACKING 0.33Kg; 42pcs/14.8Kg/0.82CUFT

Download

MDR-60-24 brochure